Growatt SPF 3500-5000ES 09Fault Error09 Cause repair



Growatt SPF 3500-5000ES 09Fault repair 

09fault meaning:

Bus soft start failed


Error 09 1





Triggering condition:

1.  BUS Voltage is lower than 400V,or Bus voltage is lower than 8 times of battery voltage

OR

2.  It can’t reach target voltage in 30 seconds.

Cause: Damaged output stage

Solution: Repair by replacing all optocouplers, Diodes around optocouplers, Transformer for IGBT Driver, IGBTS

gROWATT BURNT
model

Repaired Here is the testing